DL5-100 series miniature circuit breaker




一、summarize

     The series of high-breaking miniature circuit breaker has beautiful appearance, small size, light weight, excellent and reliable performance, high breaking capacity, rapid tripping, rail installation, high flame-retardant and impact resistant plastics for shells and components, and long service life. Mainly used for AC 50Hz single-pole, two-pole 230v, three, four-pole 400V line overload, short circuit protection, but also under normal circumstances, infrequent on and off electrical devices and lighting circuits.



二、Model and its meaning


三、Technical Parameters

1. The rated current of the brake pedal is: 63A, 80A, 10OA,
2. The number of poles of circuit breakers is divided into: single pole, two poles, three poles and four poles;
3. This circuit is recessed (can be installed on the mounting rail):
4. The rated insulation voltage of the breaker and its related rated short-circuit breaking capacity are shown in Table 1;

Rated current(A)

Number of poles(P)

Frame rated current(A)

Rated voltage(V)

Rated current(A)

Rated short-circuit section capability(KA)

DL5-100

1、2、3、4

100

230/400

63、80、100

10

5.The overcurrent release of the circuit breaker is shown in Table 2.

No.

Release rated currentInA

Starting state

Test current

set time

expected outcome

Note

1

In=63

Cold

1.05In

t1h

No tripping

-

In63

Cold

1.05In

t2h

No tripping

-

2

In=63

Immediately after the previous test

1.30In

t1h

Tripping

The current rises steadily within 5s to the specified value

In63

Immediately after the previous test

1.30In

t2h

Tripping

3

In63

Cold

8.00In

t0.2s

No tripping

-

12.00In

t0.2s

No tripping

-


6. Power frequency withstand voltage: The circuit breaker shall meet the withstand voltage test of AC 50Hz and 2500V for 1min. The conventional experiment is 1s without flashover and breakdown.
7. Mechanical and electrical performance:

    The number of operation cycles of the circuit breaker is 10,000, of which the number of loaded operation cycles is 1500 and the number of no-load operation cycles is 8,500.