Products Center

Products

DLML1-225/4300 series leakage circuit breaker





一、summarize

    DLML1 series leakage circuit breakers (hereinafter referred to as leakage breakers) are one of the new types of circuit breakers that have been designed and developed by the company using international advanced technology. Suitable for leakage protection in AC 50/60Hz, rated operating voltage up to 400V, rated operating current from 16A to 630A in the distribution network circuit, it can also prevent the fire hazard caused by ground fault current due to equipment insulation damage. Can be used to allocate power and protect the line and power supply equipment from overload, short circuit and other damage, can also be used as the motor's infrequent start and overload, short circuit protection.
    The leakage circuit breaker has the characteristics of small volume (the same volume of the corresponding molded case circuit breaker), high breaking, short arcing, and adjustable residual operating current, and can also be provided with an alarm contact, a shunt release, and an auxiliary touch. First-class accessories are ideal for users.
    Leakage circuit breakers are installed vertically (ie, vertically) and can also be installed horizontally (ie, horizontally).
    This product complies with GB6829idtIEC60755. GB14048.2idtIEC60947-2 standard.

二、model and its meaning



三、functional characteristics
Leakage current I △ n (adjustable): (30) 50mA-500mA.
Leakage action time (adjustable): non-delay <0.1s, delay 0.2s/0.4s/0.8s (1s).
Digital display actual leakage current.
Earth leakage trip indication: light emitting diodes.
Leakage alarm and trip function:
1 Trip after alarm - The alarm starts when the leakage current reaches 0.65I △ n ± 10%, and the tripping action occurs when the leakage current reaches 0.8 I △ n ± 10%.
2 alarms do not trip - alarm when the electric current reaches I △ n ± 10%, but cannot trip.
3 alarm form - the sound signal of the buzzer in the circuit breaker.
           - External use special auxiliary contact action (contact capacity AC220V, 1A)




四、classification


3.1Divided by the number of poles

3.2According to the mode of operation

3.3According to the wiring method

3.4According to rated leakage action time

3.5Overcurrent release type

Quadrupole(4P

Handle directly

Board wiring

Delay type (adjustable)

Instantaneous trip type

Three-pole four-wire(3N

Electric mechanism operation

Post-board wiring

Non-delay(<0.1s

Duplex trip type

 

Turn handle operation

 

 

 


accessory name/
Attachment code /
Overcurrent tripping

 

Without accessories

 

Alarm contact

Shunt release

Auxiliary contact

Undervoltage release

Instantaneous release

200

208

210

220

230

Duplex release

300

308

310

320

330



五、Normal use conditions
  4.1 Ambient air temperature
  4.1.1 The upper limit of ambient air temperature is +40°C;
  4.1.2 The lower limit of ambient air temperature is -5°C;
  4.1.3 The average ambient air temperature 24h does not exceed +35 °C;
4.2 Altitude: The altitude of the installation site does not exceed 2000m.
4.3 Pollution Level: 3.
4.4 Installation Category: III
4.5 Atmospheric conditions: Atmospheric relative humidity does not exceed 50% at ambient air temperature of +40°C; higher relative humidity may be obtained at lower temperatures; monthly average maximum relative humidity of the wetest month is 90%, and the month The monthly average minimum temperature is +25°C and takes into account the condensation that occurs on the surface of the product due to temperature changes.
4.6 External magnetic field: The external magnetic field near the place where the leakage breaker is installed shall not exceed 5 times of the geomagnetic field in any direction.

六、main technical parameters
6.1 Rated value of leakage circuit breaker

Type

Frame rated current InmA

Rated current InA

Rated operating voltage UnV

Number of poles

Rated residual operating current

InmA

Rated residual non-operating current

InmA

Rated limit short-circuit breaking capacity IcuKA

Rated operation short circuit breaking capacity IcsKA

Arc distance(mm

DLML1-100

100

1620253240506380100

400

343N

3050100200300500

152550100150250

30

15

50

DLML1-225

225

100125160180200225

400

343N

50100200300500

25、、50100150250

30

15

50

DLML1-400

400

225250315350400

400

343N

100200300500

50100150250

50

25

100

DLML1-630

630

400500630

400

343N

1002003005001000

50100150250500

65

40

100

DLML1-800

800

700800

 

343N

1002003005001000

50100150250500

65

40

100



Note: The remaining operating current of the fourth gear can be arbitrarily selected by the user.

6.2 Inverse Time Offset Characteristics of Current-Exciting Circuit Breaker Overcurrent Breaker

NO.

Test current name

I/In

Appointment time

Starting state

1

Agreement does not trip current

1.05

2hIn63A,1hIn63A

Cold

2

Agreed tripping current

1.30

2hIn63A,1hIn63A

Immediately after the first trial


6.3 Inverse time limit of the current leakage protection circuit breaker for overcurrent protection of motor protection

NO.

Setting current

Appointment time

Starting state

Inm=100A

Inm=225A400A

Inm=630A

1

1.05In

2h

2h

2h

Cold

2

1.2In

2h

2h

2h

Immediately after the first trial

3

1.5In

4min

4min

8min

Hot

4

7.2In

T1s

4sT10s

6sT20s

Cold

6.4 Residual current breaking time of leakage breaker.
6.4.1 Residual current breaking time of general earth leakage circuit breaker

Leakage current

In

2In

5In1

10In2

Non-delayed

Maximum disconnection time(s

0.2

0.1

0.01

0.04

Delay type

Maximum disconnection time(s

0.7/1.2/2.2

0.6/1/2

0.5/0.9/2

0.5/0.9/2

Limit inoperative time(s

-

0.2/0.4/0.8

-

-


Note: 1) Use 0.25A instead of 5I △n for an earth leakage circuit breaker with I△n ≤ 30mA.
    2) For leakage circuit breakers with IΔn > 30mA, substitute 0.5A for 10IΔn.
    3) If the user needs special current leakage current specifications, please indicate when ordering or design drawings.

6.5 Leakage Circuit Breaker Inverse Time Protection Characteristic Curve



七、structure and working principle



7.1 This series of residual current circuit breakers are electronic residual current circuit breakers. They are mainly composed of zero sequence transformers, electronically controlled leakage releases and circuit breakers with overload and short circuit protection. All components are installed in a pair of plastic housings. .
7.2 When there is a leakage or personal electric shock in the protected circuit, as long as the residual current reaches the setting action current value, the output signal of the secondary winding of the zero-sequence transformer triggers the conduction of the thyristor and makes it through the leakage release. Leakage circuit breakers act to shut off the power supply for leakage and electric shock protection. Working principle (see figure)
7.3 When the circuit to be protected is overloaded or short-circuited, the multi-function trip unit completes the delay or instantaneous tripping action to activate the leakage circuit breaker, thereby cutting off the overload or short circuit protection of the power supply.
7.4, use and maintenance
 The long-delay and short-circuit protection characteristics of the circuit breaker are set by the manufacturer, and the user should not adjust it arbitrarily due to no special adjustment of the equipment.
 When the main circuit is powered on, press the “Test” button. This test procedure only proves that the circuit breaker itself is normal, but it cannot indicate the specific current and time of the leakage current. (Use the test button 3 times, it should operate correctly, with load switch 3 times, there should be no malfunction). Circuit-breakers fitted with undervoltage disconnectors must be energized first. Circuit breakers can be buckled and closed again. Otherwise damage switch!
 If personal safety is directly protected by a circuit breaker, the leakage current should be selected as I △ n ≤ 30 mA (for some humid, medical applications, I △ n = 10 mA is not produced by the factory).
Tests for withstand voltage tests and insulation resistances can only be made between relative grounds. The above test cannot be performed between phases because of the presence of electronic components in the product.
The leakage circuit breaker is marked with the power supply side (Example 1.3.5) and the load side (Example 2.4.6). The wiring must be installed as specified and cannot be poured into the line. Because the inverted line will burn out electronic components when the leakage action occurs.


Three-phase load imbalance should be controlled within 25%.

 Check the insulation resistance of the low-voltage network to the ground before installation.

 The electrician should check the leakage protection function with the “test button” periodically (eg 1 month). It is strictly forbidden to use the phase line to make direct contact with the zero line to do the motion check.
Electricians should conduct inspections on a regular basis, timely detect operational failures, and deal with them in a timely manner.
 If a newly installed circuit breaker is found to be “false jump”, it should be checked in time for repeated grounding or unacceptable grounding resistance or incorrect wiring, phase-neutral wire reversal, and so on.
 When the user observes the conditions of storage and use, from the date of shipment from the factory, no more than 18 months, the seal is in good condition. If it is a factory quality problem, the factory is responsible for replacement or repair.

八、shape and installation size

Type

Frame rated current(A

Number of poles

 

Installation size

A

B

D

a

b

Φd

DLML1-100

100

3

90.5

195

110

20±0.14

167±032

2-φ5+0.32 0

4

120

195

86.5

60±0.20

167±032

4-φ5+0.32 0

3N

120

155.5

86.5

60±0.20

167±032

4-φ5+0.32 0

DLML1-225

225

3

105

213

110

35±0.16

170±032

4-φ5+0.32 0

4

140

213

110

70±0.23

170±032

4-φ5+0.32 0

3N

140

213

110

70±0.23

170±032

4-φ5+0.32 0

DLML1-400

400

4

182.5

303

155

44±0.26

240±043

4-φ7+0.33 0

3N

183.5

303

155

44±0.26

240±043

4-φ7+0.33 0

DLML1-630

630

4

280

342

155

70±0.23

310±043

4-φ7+0.33 0

3N

280

342

155

70±0.23

310±043

4-φ7+0.33 0

DLML1-800

800

4

342

342

155

70±0.23

310±043

4-φ7+0.33 0

3N

342

342

155

70±0.23

310±043

4-φ7+0.33 0


九、selection principle
9.1 When selecting the rated residual operating current value of the leakage breaker, the normal leakage current value of the protected circuit and equipment shall be fully taken into account. If necessary, the leakage current value of the protected circuit or equipment may be obtained through actual measurement.
9.2. The rated residual operating current of the residual current circuit breaker shall not be less than 2 times the maximum value of the normal leakage current of the electrical circuit and equipment.
9.3. For hand-held power tools, mobile electric appliances, household appliances, sockets, and construction site electrical appliances (rated current of not less than 100A) and other equipment grounding difficulties, the residual current breakers with a rated residual operating current of 30mA or less should be preferred.
9.4 Single earth leakage circuit breakers with a rated residual operating current of 3 mA or less may be used for a single device. The total protection of multiple devices (multi-branch) should use residual current circuit breakers with rated residual operating current of 30mA or more.
9.5、Electrical equipment installed in a wet place should use a residual current circuit breaker with a rated residual operating current of 30mA or less.

十、ordering instructions
The user must specify when ordering:
10.1 Type and name of leakage circuit breaker;
10.2 Rated current of an overcurrent release of an earth leakage circuit breaker;
10.3 Rated residual operating current of leakage breakers;
10.4 Breaking time of leakage breaker;
10.5. Types of protection, number of poles, and quantities;
10.6 Rated voltage of internal leakage breaker accessories and external accessories.
      For example: order DLML1-100P/3310 leakage circuit breaker, overcurrent release rated current 40A, rated
      Residual operating current 30/50/100mA (adjustable in third gear), breaking time <0.2s,
      3-pole with shunt release (AC230V), electric operating mechanism (AC230V), for distribution protection, quantity
10 equipment.


Copyright 2017-2018 DeLong Electric Co., Ltd. All Rights Reserved.