Products Center

Products

DL7NL-40 (Phase + Neutral) Leakage Circuit Breaker


一、summarize


    DRNL-32 is a new product independently developed by our company (this product integrates the advantages of the same type of product) has the advantages of compact structure, small size, excellent performance, small size, high breaking capacity, and full protection function. Products comply with GB16917.1, Gb10963 and other standards, in a similar product in a leading position.

二、 scope of application


    DL7NL-40 leakage circuit breaker (hereinafter referred to as leakage circuit breaker) (phase line + neutral line + leakage) protection circuit breaker is suitable for AC 50Hz or 60Hz, rated voltage 230V single-phase residential circuit, as a leakage protection, It also protects the overload and short circuit of the civil electric circuit. The product has a high capacity for small volume breaking. The zero and fire lines are cut off at the same time, and even if the fire line is reversed, the leakage can still be protected. This product complies with IEC61009/GB16917.1 and other standards.

三、product model and its main meaning

四、specifications


Rated voltage(V) Rated current(A) Rated residual operating currentI△N(mA) Rated residual non-operating currentI△NO(mA) Maximum breaking time(s) Rated short-circuit breaking capacity(A) Rated residual on-off breaking capacity(A)
I△N 2I△N 0.25A 500A
240 6、10、16、20、25、32、40 30、100 15、50 0.1 0.05 0.04 0.04 6-20A 6kA25-40A 4.5kA 500




五、 Main technical parameters


Test current(A)

Rated current

Starting state

Test time(t)

test results

Note

6、10、16、20、25、32、40

1.13IN

Cold

≥1h

No tripping


1.45IN

Hot

<1h

Tripping

The current rises steadily within 5s to the specified value

2.55IN

Cold

1-60s

Tripping


5IN

Cold

≥0.1s

No tripping


10IN

Cold

<0.1s

Tripping



Residual current protection characteristics of residual current circuit breakers are given in the table below

Rated residual operating currentIN(mA) Rated residual non-operating currentINO(mA) Maximum breaking time(s)
30、100 15、50 0.1



六、installation and wiring diagram


Read carefully before installation and install it correctly

1 pull down the DIN rail, install the card
2 Lift it up while tilting the unit
Note: When the DIN rail mounting card is pulled out, it will be locked. Therefore, before reinstalling the unit on a DIN rail, push it inward.

七、compared with similar products


     DL7NL-40 advantages: only 1 module, saving half of the distribution box space compared to LD7, breaking capacity of 6KA to obtain 2 utility model patents and 1 appearance patent.

八、ordering instructions


1, product model, name; 2, pole number; 3, rated current; 4, rated residual operating current; 5, order quantity.

Copyright 2017-2018 DeLong Electric Co., Ltd. All Rights Reserved.